IEEE 14-Bus N-1 Contingency Analysis
Full AC outage analysis with transparent synthetic thermal ratings and DC/LODF screening.
259.0 MW
Base load13.39 MW
Base losses3
Base voltage violations0
Base thermal violations1
Islanding outagesInterpretation guardrail: the canonical case omits branch ratings. Thermal percentages use a documented study rating: 25% base-case MVA headroom, rounded up to 5 MVA, with a 40 MVA floor. They are scenario results, not utility equipment ratings.
Top five contingencies
| Rank | Outage | Score | Status | Max loading | Voltage violations |
|---|---|---|---|---|---|
| 1 | T04 7-8 | 1750.00 | Islanding | N/A% | 0 |
| 2 | L01 1-2 | 349.73 | Converged | 277.60% | 2 |
| 3 | L03 2-3 | 291.71 | Converged | 263.79% | 2 |
| 4 | T03 5-6 | 177.96 | Converged | 148.73% | 6 |
| 5 | L02 1-5 | 117.35 | Converged | 141.81% | 2 |
Additional non-islanding non-convergent cases: 0. See CSV files for bus- and branch-level detail.