IEEE 14-Bus N-1 Contingency Analysis

Full AC outage analysis with transparent synthetic thermal ratings and DC/LODF screening.

259.0 MW
Base load
13.39 MW
Base losses
3
Base voltage violations
0
Base thermal violations
1
Islanding outages
Interpretation guardrail: the canonical case omits branch ratings. Thermal percentages use a documented study rating: 25% base-case MVA headroom, rounded up to 5 MVA, with a 40 MVA floor. They are scenario results, not utility equipment ratings.

Top five contingencies

RankOutageScoreStatusMax loadingVoltage violations
1T04 7-81750.00IslandingN/A%0
2L01 1-2349.73Converged277.60%2
3L03 2-3291.71Converged263.79%2
4T03 5-6177.96Converged148.73%6
5L02 1-5117.35Converged141.81%2

Additional non-islanding non-convergent cases: 0. See CSV files for bus- and branch-level detail.